4-102
Motor core loss (02-13)
Set motor core loss as the percentage of the motor rated power
Note:In V/F mode motor core loss (o2-13) is used to for torque compensation.
02-15 Resistance between wires of motor 1
Range 1~60.000
02-16 Rotor resistance gain
Range 1~60.000
02-17 Resistance between wires of motor <1>
Range 1~60.000
02- 19 No-Load Voltage of motor 1
Range 【0.01~600.00】A
02- 20 No-Load Current of motor 2
Range 【0.01~600.00】A
02- 21 Rated current of motor 2
Range 10%~200% of inverter rated current
02-22 Rated rotation speed of motor 2
Range 【0~60000】rpm
02- 23 Rated voltage of motor 2
Range
200V:【50.0~240.0】V
400V:【100.0~480.0】V
02- 24 Rated power of motor 2
Range 【0.01~600.00】KW
02-25 Rated frequency of motor 2
Range 【4.8~599.0】Hz
02-26 Pole of motor 2
Range 【2~16】
02-32 Resistance between wires of motor 2
Range 【0.001~60.000】Ω
02-33 Proportion of Motor Leakage Inductance <1>
Range 【0.1~15.0】%
Im : 02-09 Excitation Current
Ks1: 02-10 Motor Core Saturation Coefficients 1
Ks2: 02-11 Motor Core Saturation Coefficients 2
Ks3: 02-12 Motor Core Saturation Coefficients 3