4-61 
4.3 Description of parameters 
Group 00 Basic Parameters 
 
00- 00  Control Mode Selection 
Range 
【0】: V/F     
【2】: SLV 
【5】: PMSLV 
 
  The inverter offers the following control modes: 
00-00 
Value 
Mode  Information  Application 
0  V/F  V/F Control without PG 
General Purpose applications which do not 
require high precision speed control, 
auto-tuning is not required. 
2  SLV 
Sensorless Vector Control without 
PG 
General Purpose Applications that   
require higher precision speed control   
and torque response without the use   
of an encoder. 
5  PMSLV 
Sensorless Current Vector   
Control without PG (for   
Permanent magnet motor) 
Without PG Applications. Provide the   
requirements of high precision speed   
and torque 
(1)  00-00=0 (V/F Mode) 
  Select the required V/F curve (01-00) based on your motor and applications. 
  Perform a stationary auto-tune (17-00=2), if the motor cable is longer than 50m   
(165ft), see parameter group 17 for details. 
 
(2)  00-00=2 (SLV Control) 
  Verify the inverter rating matches the motor rating. Perform rotational auto-tune to   
measure and store motor parameters for higher performance operation. Perform   
non-rotational auto-tune if it is not possible to rotate the motor during auto-tune.   
Refer to parameter group 17 for details on auto-tuning. 
 
(3)  00-00=5 (PMSLV) 
  PMSLV control mode has to connect motor, otherwise “CF08” error will be displayed. 
  Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure 
and store motor parameters for higher performance operation.   
  Perform auto-tuning before operation to enhance the performance of PMSLV mode. Refer to 
parameter 22-21 for the descriptions of PM motor tuning function. 
  Select the appropriate motor rating and braking resistor based on your motor and   
applications. Please install the braking module in the models of 200V 30HP/ 400V   
40HP or the above. 
 
Note:Parameter 00-00 is excluded from initialization.