Loading...
4-61
4.3 Description of parameters
Group 00 Basic Parameters
00- 00 Control Mode Selection
Range
0: V/F
【2】: SLV
【5】: PMSLV
The inverter offers the following control modes:
00-00
Value
Mode Information Application
0 V/F V/F Control without PG
General Purpose applications which do not
require high precision speed control,
auto-tuning is not required.
2 SLV
Sensorless Vector Control without
PG
General Purpose Applications that
require higher precision speed control
and torque response without the use
of an encoder.
5 PMSLV
Sensorless Current Vector
Control without PG (for
Permanent magnet motor)
Without PG Applications. Provide the
requirements of high precision speed
and torque
(1) 00-00=0 (V/F Mode)
Select the required V/F curve (01-00) based on your motor and applications.
Perform a stationary auto-tune (17-00=2), if the motor cable is longer than 50m
(165ft), see parameter group 17 for details.
(2) 00-00=2 (SLV Control)
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to
measure and store motor parameters for higher performance operation. Perform
non-rotational auto-tune if it is not possible to rotate the motor during auto-tune.
Refer to parameter group 17 for details on auto-tuning.
(3) 00-00=5 (PMSLV)
PMSLV control mode has to connect motor, otherwise CF08 error will be displayed.
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure
and store motor parameters for higher performance operation.
Perform auto-tuning before operation to enhance the performance of PMSLV mode. Refer to
parameter 22-21 for the descriptions of PM motor tuning function.
Select the appropriate motor rating and braking resistor based on your motor and
applications. Please install the braking module in the models of 200V 30HP/ 400V
40HP or the above.
Note:Parameter 00-00 is excluded from initialization.