4-41
Group 12 Monitoring Parameters
Code Parameters Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
0000 0000
Input Terminal(S8)
Input Terminal(S7)
Input Terminal(S6)
Input Terminal(S5)
Input Terminal(S4)
Input Terminal(S3)
Input Terminal(S2)
Input Terminal(S1)
0:OPEN
1:CLOSE
000
Output Terminal(DO1)
Output Terminal(R2)
Output Terminal(R1)
0
Output Terminal(PLC)
LED display is shown as below
no input
Correspondences to input and output
12-11
Output Current of
Current Fault
Display the output current of current fault
- A O O O *4
12-12
Output Voltage of
Current Fault
Display the output voltage of current
fault
- V O O O *4
12-13
Output Frequency of
Current Fault
Display the output frequency of current
fault
- Hz O O O *4
12-14
DC Voltage of
Current Fault
Display the DC voltage of current fault
- V O O O *4
12-15
Frequency
Command of
Current Fault
Display the frequency command of
current fault
- Hz O O O *4
12-16
Frequency
Command
If LED enters this parameter, it only allows
monitoring frequency command.
- Hz O O O *4
12-17
Output Frequency Display the current output frequency
- Hz O O O *4
12-18
Output Current Display the current output current
- A O O O *4
12-19
Output Voltage Display the current output voltage
- V O O O *4
12-20
DC Voltage (Vdc) Display the current DC voltage
- V O O O *4
12-21
Output Power Display the current output power
- kW O O O *4
12-28
Motor Torque
Current (Iq)
Display the current q-axis current
% X O O *4
12-29
Motor Excitation
Current (Id)
Display the current d-axis current
% X O O *4
12-36
PID Input Display input error of the PID controller
% O O O *4