4- 242
4.4 Built-in PLC function
The PLC ladder logic can be created and downloaded by TECO DriveLink software.
4.4.1 Basic Command
P
NO / NC
Inputs I i I1I8 / i1i8
Outputs Q Q Q Q Q q Q1Q2 / q1q2
Auxiliary command M M M M M m M1MF / m1mF
Special registers V1~V7
Counter function C C c C1~C8 / c1~c8
Timer function T T t T1T8 / t1t8
Analog comparison
function
G G g G1G8 / g1g8
Operation control function F F f F1~F8 / f1~f8
summation and
subtraction function
AS AS1~4
Multiplication and division
function
MD MD1~4
Description of special registers
V1:Set frequency Range:0.1~599.0Hz
V2:Operation frequency Range:0.1~599.0Hz
V3:AI1 input value Range:0~1000
V4:AI2 input value Range:0~1000
V5:Keypad input value Range:0~1000
V6:Operation current Range:0.1~999.9A
V7:Torque value Range:0.1~200.0%
Command Upper Differential Lower Differential Other command symbol
Differential command D d
SET command
RESET command
P command P
Open circuit “ “
Short circuit “--”
Connection symbol Definition
─ Connect components on the left and right side
┴ Connects components on the left , right and top side
┼ Connects components on the left , right , top and bottom side
┬ Connects components on the left , right and bottom side