3-3
Tighting Torque for Terminals
Model
TM1(Power Terminal)
Wiring Size Tighting Torque
AWG
mm
2
kgf.cm lbf.in Nm
Frame 1(200V) 14 2.5 9.8 8.5 0.96
Frame 1(400V) 14-12 2.5-10 9.8 8.5 0.96
Frame 2(200V) 14-12 2.5-4 18.4 15.9 1.8
Frame 2(400V) 14-8 2.5-10 18.4 15.9 1.8
Frame 3 12-6 4-16 24.5 21.2 2.4
Frame 4 8 10 24.5 21.2 2.4
Frame 5 6 16 30 26 2.9
Frame 6 0 50 81.7 70.7 8
Model
TM2(Control Terminal)
Wiring Size Tighting Torque
AWG
mm
2
kgf.cm lbf.in Nm
Frame 1~2 26~18 0.5~0.15 5.7 5 0.56
Frame 3~4 16 0.5~0.15 8 7 0.79
Frame 5~6 14 0.5~0.15 8 7 0.79
Specifications for terminals
Frame size Horsepower
Power
specification
Voltage
(Volt)
Current
(A)
Frame1
0.5/1/2(-H3) 200V~240V
600 20
1/2 380V~480V
Frame2
2(-H)/3/5 200V~240V
600 45
3/5 380V~480V
Frame 3/4
7.5/10/15/20 200V~240V 600 100
7.5/10/15/20/25 380V~480V 600 65
Frame 5
25 200V~240V 600 100
30 380V~480V 600 75
Frame 6
30/40 200V~240V 600
175
40/50/60/75 380V~480V 600