6-6 
 
Model 
Braking   
Unit 
Specifications of Braking Resistor
Dimension of 
Braking Resistor 
Braking 
Torque
Minimum
Resistance
V  HP  KW  Model  Qty
Number of Braking 
Resistor   
Qty (W) (Ω )
(LxWxH) 
mm 
Qty 
10% 
ED 
(Ω ) (W)
 
20  15  -  - JNBR-1R5KW40  1 1500 40
1500W/40Ω  
(615x60x110) 
1  119  22  3000
25  18.5  -  - JNBR-4R8KW32  1 4800 32
1200W/32Ω  
(535x60x110) 
4  117  14  4800
30  22  -  - JNBR-4R8KW27R2 1 4800 27.2
1200W/27.2Ω  
(535x60x110) 
4  117  14  4800
40  30  -  - JNBR-6KW20  1 6000 20
1500W/20Ω  
(615x60x110) 
4  119  11  6000
50  37  TBU-430  2 JNBR-4R8KW32  2 4800 32
1200W/32Ω  
(535x60x110) 
8  119  19.2 3600
60  45  TBU-430  2 JNBR-4R8KW27R2 2 4800 27.2
1200W/27.2Ω  
(535x60x110) 
8  117  19.2 3600
75  55  TBU-430  2 JNBR-6KW20  2 6000 20
1500W/20Ω  
(615x60x110) 
8  126  19.2 3600
Note: 
Formula for brake resistor:W= (Vpnb * Vpnb) * ED% / Rmin 
(1)  W:braking resistor power (Watts) 
(2)  Vpnb:braking voltage (220V=380VDC, 440V=760VDC) 
(3)  ED%:braking effective period 
(4)  Rmin:braking resistor minimum value (ohms) 
 
6.6 Input noise filter 
Install a noise filter on power supply side to eliminate noise transmitted between the power 
line and the inverter. The inverter noise filter shown in table belowmeets the EN61800-5-1.   
Frame  Model  Input Voltage  Number of Filter  (A) 
1  2P5/201-SH 
1Φ /3Φ   200~240V 
E2F-2102/FN3258-16-45  10/16 
2  202/203-SH1(F)  FS6146-27-07/FN3258-16-45  27/16 
1  202-SH3 
3Φ   200~240V 
FN3258-16-45  16 
2  205-SH3  FS20500-22-99  22 
3  208/210-SH3  T-096.05001.00  50 
4  215/220-SH3  T-097.08004.00  80 
5  225-SH3  FS32125-86-99  86 
6  230/240-SH3  FS32125-150-99  150 
1  401/402-SH3(F) 
3Φ   380~480V 
FN3258-16-45  16 
2  403/405-SH3(F) 
3  408/410/415-SH3(F)  T-097.08004.00  80 
4  420/425-SH3(F)  FS42500-50-99  80 
5  430-SH3(F)  JN5-FLT-63A  63 
6  440/450/460-SH3(F)  JN5-FLT-112A  112 
6  475-SH3(F)  FS32126-181-99  181