3-36
3.4.4 Capacitor Reforming Guide After Long Storage
For correct performance of this product after long storage before use it is important that Inverter
Capacitors are reformed according to the guide below:
Storage
time
Procedure to re-apply voltage
≦1year Apply rated voltage of inverter in the normal way
Between
1-2 years
Apply rated voltage of inverter(Note1) to the product for one hour before using the
inverter
≧2 years
Use a variable AC power supply to
1. Connecting 25% rated voltage of inverter for 30 minutes.
2. Connecting 50% rated voltage of inverter for 30 minutes.
3. Connecting 75% rated voltage of inverter for 30 minutes.
4. Connecting 100% rated voltage of inverter for 210 minutes.
Once the procedures completed, inverter just can be used normally
Note1:Please refer the rated voltage according to model label of inverter