3.4.2 General specifications
Item
E510s
Control mode V/F, SLV, PMSLV control mode
Frequency
Output Frequency 0.01~599.00Hz
Starting Torque 150% / 1Hz (SLV mode),150% / 3Hz(V/F mode)
Frequency resolution
Digital input:0.01Hz
Analog input:0.06Hz/60Hz
Frequency setting
Keypad:set directly with ▲▼keys or the VR on the keypad
External input terminals: AI1、AI2 (0/2-10V, 0/4-20mA)
Multifunction input UP/DOWN function(Group 3)
Set frequency by communication method
Frequency limit Lower and upper frequency limits 3 skip frequency settings.
Run Operation set
Keypad RUN/STOP buttom
External terminals:
Multi-operation mode 2/3 wires selection
JOG operation
Run signal by communication method
Main
Control
Features
V / F curve setting 15 fixed curves and 1 customized curve
Carrier frequency 1~16kHz (factory setting is 5kHz)
Acceleration and
deceleration control
2 off acceleration/deceleration time parameters
4 off S curves parameters
Multifunction input Refer to description on Group 3
Multifunction output Refer to description on Group 3
Multifunction analog output Refer to description on Group 4
Main features
Overload detection, 16 preset speed, Auto-run, Acc/Dec
switch(2 stages), Main/Alt run command select, Main/Alt
frequency command select, PID control, Torque boost, V/F
start frequency, Fault reset, Fire mode, Multi-Pump function.
Display
LED display
Parameter, Paramete value, Frequency, Line speed, DC
voltage, Output voltage, Output current, PID feedback, Input
and output terminal status, Heat sink temperature, Firmware
version, Fault list.
LED status indicator Run, Stop, Forward, Reverse and etc.
Protective
Functions
Overload protection (OL1) Electrical overload protection curve
Overload protection (OL2)
H.D mode:150% for 60s (200% for 2s)
N.D mode:120% for 60s
Over voltage
200V Class:DC bus voltage higher than 410Vdc
400V Class:DC bus voltage higher than 820Vdc
Under Voltage
200V Class:DC bus voltage lower than 190V
400V Class:DC bus voltage lower than 380V
Momentary Power Loss
Restart
Inverter auto-restart after a momentary power loss
Stall Prevention
Stall prevention for acceleration/deceleration operation
Short-circuit output terminal
Electronic circuit protection
Grounding Fault
Electronic circuit protection
Other protection features
Protection for overheating of heat sink, Fault output, Reverse
prohibit, Prohibit for direct start after power up and error
recovery, Parameter lock up, STO (Safety Torque Off).