1-2 
  RCD is required to be in compliance with the protection norm of B-type leakage 
current. 
  Please check and test emergency stop circuits after wiring. (Installer is responsible 
for the correct wiring.) 
  Never touch any of the input or output power lines directly or allow any input of 
output power lines to come in contact with the inverter case. 
  Do not perform a dielectric voltage withstand test (megger) on the inverter this 
will result in inverter damage to the semiconductor components. 
  Caution 
  The line voltage applied must comply with the inverter’s specified input 
voltage. 
  Connect braking resistor and braking unit to the designated terminals. 
  Do not connect a braking resistor directly to the DC terminals P (+) and N (-), 
otherwise fire may result. 
  Use wire gauge recommendations and torque specifications. 
  Never connect input power to the inverter output terminals U/T1, V/T2, W/T3. 
  Do not connect a power factor correction capacitor or surge suppressor to the 
inverter output. 
  Ensure the interference generated by the inverter and motor does not affect 
peripheral devices. 
 Danger 
  When the momentary power loss is longer than 2 seconds, the inverter will not 
have sufficient stored power for its control circuit. Therefore, when the power is 
re-applied, the run operation of the inverter will be based on the setting value of 
parameter 00-02(or 00-03) and 07-04 status of external run switch. 
  When the momentary power loss is shorter, inverter still can control the power. 
Therefore, when the power is re-applied, the run operation of inverter will be 
based on the setting value of parameter 07-00. 
  When the power is re-applied, the run operation of inverter will be based on the   
setting value of 00- 02(or 00- 03), 07- 04 and the status of power and operation 
switch(FWD/REVswitch)(and 07- 00/07- 01/07- 02): 
(1)  If the parameter 00-02(or 00- 03)=0, inverter will not start automatically 
when the power in re-applied. 
(2)  If the parameter 00- 02(or 00- 03)=1 and the power or operation switch is 
open, inverter will not start automatically when the power is re-applied. 
(3)  If 00- 02(or 00- 03)=1, then power and operation switch are open   
(07- 04=0), inverter will restart automatically when the power is re-applied.   
For the safety, please turn off the power and operation switch after powered 
off. 
  For the safety, please read the function explanation from the manual. 
1.3  Before Operation 
 Caution   
  Make sure the inverter  model  and rating are the same as that  set  in  parameter 
13-00.