4-232
23- 13 Warning Time of High Pressure
Range 【0.0 ~ 600.0】Sec
When pressure feedback value is higher than maximum pressure limit, warning time of high
pressure starts to count. If pressure feedback value is lower than maximum pressure limit
during counting time, the warning time will recount and the inverter will display the warning
signal of HIPb when the warning time ends.
23- 14 Stop Time of High Pressure
Range 【0.0 ~ 600.0】Sec
When the warning signal of high pressure occurs and pressure feedback value is higher than
maximum pressure limit, stop time of high pressure starts to count. If pressure feedback value
is lower than maximum pressure limit during counting time, the stop time will recount and the
inverter will display stop error signal of OPbFt when the stop time ends.
Note:
When user does not want the inverter to be restricted by the maximum pressure, set 23-74=0
(disable) to disable the function of high pressure limit.
Fig. 4.3.105 Diagram for warning to stop at high pressure limit
23- 16 Warning Time of Low Pressure
Range 【0.0 ~ 600.0】Sec
When pressure feedback value is lower than minimum pressure limit, warning time of low
pressure starts to count. If pressure feedback value is higher than minimum pressure limit
during counting time, the warning time will recount and the inverter will display the warning
signal of LoPb when the warning time ends.