4-239
23-35=3, Timer alternately selected and sleep stop alternately selected will be enabled at the
same time.
23-35=4, When master stop running and the slave need to run, please set 23-35=4, and no
exchange between Master and Slave.
23-37 Leakage Detection Time
Range 【0.0~100.0】Sec
23-38 Pressure Variation of Leakage Detection Restart
Range 【0.01~65.00】PSI
23-39 Pressure Tolerance Range of Leakage Detection Restart
Range 【0.01~650.00】PSI
To limit single inverter to use leakage detection.
When 23-37 = 0.0 (sec), switch off this function.
When pump is at shutdown state, pressure will drop over time if pipeline leaks. Pump will
restart if pressure variation is larger than the value of parameter 23-38 in every detection time
(23-37).