5-6
LED display Description Cause Possible solutions
FBLSS
PID Feedback Signal Loss
Since proportion of loss pressure
(23-19) is enabled and over high,
the inverter trips to fault. Thus,
feedback sensor cannot operate
properly or is not installed
correctly.
Check if the proportion of
loss pressure (23-19) is set
correctly.
Make sure the feedback
sensor is installed correctly
and PID feedback signal
operates normally.
Short Circuit
Inverter output short
circuit or ground fault.
Short circuit or ground fault
(08-23 = 1).
Motor damaged (insulation).
Wire damage or deterioration.
Check the motor wiring.
Disconnect motor and try
running inverter.
run
Motor1/Motor2
Switch
Motor1/Motor2 switch
during operation
Input motor 2 switch command
during operation.
Improve the control
sequence, motor can be
switched in stop.
PF
Protection Error
1. OH1/OL2 error occurs
three times in 5
minutes.
2. Digital input or
communication run
command not
removed
Digital input or communication
runcommand not removed.
Remove the digital input or
communication run
command.
LPBFT
Low pressure fault
The feedback signal is not
connected.
Since feedback value of pump
pressure is lower than limit of
minimum flow.
Check feedback signal is
correct and with
connection.
Check if feedback value of
pressure is lower than limit
of minimum pressure
(23-15).
OPBFT
High pressure fault
Since feedback value of pump
pressure is lower than limit of
maximum flow.
Check feedback signal is
correct.
Check if feedback value of
pressure is lower than limit
of maximum pressure
(23-12).
TOL
External Overload
(For fire mode only)
External Overload signal receied
by digital input terminal
Check the reason for
external overload
Reset digital input terminal
of external overload
FB(Flash)
PID feedback breaking
Feedback signal wire broken
Feedback sensor broken.
Check feedback wiring
Replace feedback sensor.