5-8
LED display Description Cause Possible solutions
OL2
Inverter
overload
Inverter thermal
overload protection
tripped.
If an inverter overload
occurs 4 times in five
minutes, it is required to
wait 4 minutes before
resetting the fault.
Voltage setting V/F mode too
high, resulting in
over-excitation of the motor.
Inverter rating too small.
Load too heavy.
Check V/f curve.
Replace inverter with larger
rating.
Check and reduce motor
load, check and operation
duty cycle.
Comm. Error
No Modbus
communication
received in for the time
specified in 09-06
(communication error
detection time).
Active when 09-07(= 0
to 2).
Connection lost or wire broken.
Host stopped communicating.
Check connection
Check host computer /
software.
Retry (flash)
Automatic reset
activated, warning is
displayed until restart
delay time set (07-01)
expires.
Parameter 07-01 set to a value
greater than 0.
Parameter 07-02 set to a value
greater than 0.
Warning disappears after
automatic reset.
ES (flash)
External
Emergency
Stop
External emergency stop
Enabled.
03-00~03-05 set to 14, and the
digital input enabled.
Turn off run command, and
remove external
emergency stop command.
bb1 (flash)
External
baseblock
External base block
(Terminal S1)
Multifunction digital input
external baseblock active.
Multi-function input
function set incorrectly.
Check wiring
bb2 (flash)
External
baseblock
External base block
(Terminal S2)
bb3 (flash)
External
baseblock
External base block
(Terminal S3)