3-25
PUMP Wiring Diagram for PressureSensor of Current Type
Single Pump:
Multi-Pump:
E510s Multi-Pump Operation: Follower 2 E510s Multi-Pump Operation: Follower 3
Operation
Switch
TM2
10V AOAGND
AI2
S(+) S(-) SF1 SG SF2 COM S2 S4 S6
S1 S3 S5 24V AI1R2A R2B R1A R1B R1C
TM2
00-02 = 1 (Control Circuit Terminal); 04-00 = 1 (4~20mA)
10-00 = 0 (Target Source: KeyPad); 10-01 = 2 (Feedback Source: AI2)
10-03 = XXX1b (PID is enabled), 23-00 = 1 (PUMP); 23-01 = 1 (Master)
NPN
PNP
I
V
10V AOAGND
AI2
S(+) S(-) SF1 SG SF2 COM S2 S4 S6
S1 S3 S5 24V AI1R2A R2B R1A R1B R1C
10V AOAGND
AI2
S(+) S(-) SF1 SG SF2 COM S2 S4 S6
S1 S3 S5 24V AI1R2A R2B R1A R1B R1C
10V AOAGND
AI2
S(+) S(-) SF1 SG SF2 COM S2 S4 S6
S1 S3 S5 24V AI1R2A R2B R1A R1B R1C
JP1
JP3
Master
NPN
I
V
JP1
Follower
JP3
PNP
00-02 = 1 (Control Circuit Terminal); 04-00 = 1 (4~20mA)
10-00 = 0 (Target Source: KeyPad); 10-01 = 2 (Feedback Source: AI2)
10-03 = XXX1b (PID is enabled), 23-00 = 1 (PUMP); 23-01 = 2 (Follower 1)
00-02 = 1 (Control Circuit Terminal); 04-00 = 1 (4~20mA)
10-00 = 0 (Target Source: KeyPad); 10-01 = 2 (Feedback Source: AI2)
10-03 = XXX1b (PID is enabled), 23-00 = 1 (PUMP); 23-01 = 3
(Follower 2)
00-02 = 1 (Control Circuit Terminal); 04-00 = 1 (4~20mA)
10-00 = 0 (Target Source: KeyPad); 10-01 = 2 (Feedback Source: AI2)
10-03 = XXX1b (PID is enabled), 23-00 = 1 (PUMP); 23-01 = 4
(Follower 3)
Notes1: The position of dip switch requires being correct (JP1,JP3), it is required to reconnect
the power after setting Master/Slave.
Notes2: When the communication modes is selected to be multiple pumps in parallel
connection (09-01=3), the baud rate settings 09-02 of Master and Slave are required
to be consistent.