3-28
Model:E510-□□□-SH3 225 230 240
Horse power (HP) 25 30 40
HD/ND Suitable motor capacity (kW) 18.5/22 22/30 30/37
HD/ND Rated output current (A) 73/80 85/110 115/138
HD/ND Rated capacity (KVA) 27.8/30.1 32.4/41.9 43.8/52.6
Input voltage range(V) Three phase200~240V,50/60Hz
Allowable voltage fluctuation -15%~+10%
Output voltage range(V) Three phase:0~240V
Input current (A)* 79.4/85.9 92.4/119.6 125/150
Inverter net weight (KG) 10 30 30
Allowable momentary power loss time(s) 2.0 2.0 2.0
Enclosure IP20/NEMA1
400V Class:Three phase
Model E510-□□□-SH3(F) 401 402 403 405
Horse power (HP) 1 2 3 5
Suitable motor capacity (KW) 0.75 1.5 2.2 4.0
Rated output current (A) 2.5 3.8 5.3 9.2
Rated capacity (KVA) 1.7 2.9 4.0 6.7
Input voltage range(V) Three phase380~480V,50/60Hz
Allowable voltage fluctuation -15%~+10%
Output voltage range(V) Three phase:0 480V
Input current (A)* 4.2 5.6 7.3 11.6
Inverter net weight (KG) 1.7 1.7 2.5 2.5
Inverter net weight(with Filter) (KG) 1.9 1.9 2.8 2.8
Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0
Enclosure IP20/NEMA1
Model E510-□□□-SH3(F) 408 410 415 420 425
Horse power (HP) 7.5 10 15 20 25
Suitable motor capacity (KW) 5.5 7.5 11 15 18.5
Rated output current (A) 13.0 17.5 24 32 40
Rated capacity (KVA) 9.9 13.3 19.1 24 30.5
Input voltage range(V) Three phase380~480V,50/60Hz
Allowable voltage fluctuation -15%~+10%
Output voltage range(V) Three phase:0~480V
Input current (A)* 17 23 31 38 48
Inverter net weight (KG) 6.7 6.7 6.7 13.7 13.7
Allowable momentary power loss time(s) 2.0 2.0 2.0 2.0 2.0
Enclosure IP20/NEMA1