5-84
(2) External Analog Torque Limit: The following is External Analog Torque Limit Command
Wiring Diagram:
CN1-27
CN1-29
Driver
TIC
AG
Analog Torque
Limit Input
(±10V)
Tn103 Analog torque limit proportioner
JSDG2S-E(L) does not have this function
Initial Value Unit Setting Range Effective RS-485 Address
300 %/10V 0 ~ 600 Effective after Set 0103H
Setting Description: Used to adjust the slope of Voltage Command relative to the Torque Command
105
-5-10
Torque Limit
(%)
Input
Voltage (V)
Slope is set
by Tn103
400
200
-400
-200
600
-600
Attention
The input voltage of analog torque limit voltage command does not have polarity. + voltage
or – voltage are received as an absolute value. The speed limit of this absolute value is applied
to forward and reverse direction.
When using External Analog Torque Command Limit, if this Analog Torque Command Limit
is greater than the Internal Torque Command Limit, then the Internal Torque Command
Limit is ultimately used.
Add a filter to the analog torque command (TIC) to smooth the torque command. The analog torque
command filter is set by Tn116. When the set value is too low, the response of the torque command
may decrease. Please confirm the response while setting.
Tn116 Analog torque command filter
Initial Value Unit Setting Range Effective RS-485 Address
0 Hz 0 ~ 5000 Effective after Set 0110H
Setting Description: Set TIC analog torque command stop frequency, if set 2500, it means 2500Hz.