5-85
 
5-4-9 Other Position Control Functions 
This Section describes other functions related to Position Control. 
 
Positioning Completed Function 
When Position Error is lower than the number of Pulses set by Pn307 (Positioning Completed 
Determined Value), Digital Output Contact INP operates. Refer to the following description: 
 
Pn307 Positioning Completed Determined Value 
Initial Value  Unit  Setting Range Effective  RS-485 Address 
One thousandth of a circle  pulse  0 ~ 41943040  Effective after Set  030CH/030DH 
Setting Description:  When Position Error is lower than the pulse number set by Pn307 (Positioning 
Completed Determined Value), Digital Output Contact INP operates. 
 
 
  Excessive Position Error Warning Function   
When Position Error is larger than the number of Pulses set by Pn308 (Positive Maximum 
Position Error Determined Value) or Pn309 (Negative Maximum Position Error Determined Value), 
this device generates AL.011 (Excessive Position Error Alarm). The setting is as follows: 
 
Pn308 Positive Maximum Position Error Determined Value 
Initial Value  Unit  Setting Range  Effective  RS-485 Address
5000  0.001rev 0 ~ 50000  Effective after Set  030EH 
Setting Description: When Position Error is higher than the pulse number set by Pn308 (Positive 
Maximum Position Error Determined Value), this device generates AL.011 (Excessive Position Error 
Alarm).