7-107
Hn623 Digital output contact control mode selection
【
5-6-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
H0000 -- H0000 ~ H00FF -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
0517H 2617H 2617H-- O O O O O
Setting Description: The output state of the digital output contact is determined by the bit setting method, and the bit
setting adopts the binary conversion hexadecimal method. Firstly, DO-01 ~ DO-08 correspond to the
1st ~ 8th bits of the binary, and then complete the planning binary bit is converted to hexadecimal and
then set.
Binary bit representation: 0: DO ON or OFF is determined by the function setting
1: DO ON or OFF is determined by the communication setting
Hn624 Communication control digital output contact status
【
5-6-1
】
Initial Value Unit Setting Range Effective Cn029 Reset
H0000 --
H0000 ~ H00FF
(Hexadecimal)
-- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
0518H 2618H 2618H-- O O O O O
Setting Description: The bit setting method is used to determine the contact status when the communication control digital
output contact adopts communication control; please refer to the description of Hn623 for the bit
setting method.
Binary bit representation: 0: Digital output contact OFF
1: Digital output contact ON