EasyManua.ls Logo

TECO L510 - Page 149

TECO L510
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A1-5
Recommended Input Fuse Selection
Fuse Type
Drive Model L510
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
100 V Class Single-Phase Drives
1P2
Bussmann 16CT
690V 16A
1P5
Bussmann 20CT
690V 20A
101
Bussmann 25ET
690V 25A
Fuse Type
Drive Model L510
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
200 V Class Single-Phase Drives
2P2
Bussmann 10CT
690V 10A
2P5
Bussmann 10CT/16CT
690V 10A / 690V 16A
201
Bussmann 16CT/20CT
690V 16A / 690V 20A
202
Bussmann 30FE
690V 30A
203
Bussmann 50FE
690V 50A
Fuse Type
Drive Model L510
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
200 V Class Three-Phase Drives
2P2
Bussmann 10CT
690V10A
2P5
Bussmann 10CT
690V 10A
201
Bussmann 10CT
690V 10A
202
Bussmann 16CT
690V 16A
203
Bussmann 20CT
690V 20A
Fuse Type
Drive Model L510
Manufacturer: Bussmann
Model
Fuse Ampere Rating (A)
460 V Class Three-Phase Drives
401
Bussmann 10CT
690V 10A
402
Bussmann 16CT
690V 16A
403
Bussmann 20CT
690V 20A