A1-6 
Motor Over Temperature Protection 
 
Motor over temperature protection shall be provided in the end use application. 
 
■  Field Wiring Terminals 
 
All input and output field wiring terminals not located within the motor circuit shall be marked to indicate the 
proper connections that are to be made to each terminal and indicate that copper conductors, rated 75°C 
are to be used. 
 
■  Inverter Short-Circuit Rating 
 
This inverter has undergone the UL short-circuit test, which certifies that during a short circuit in the power 
supply the current flow will not rise above value. Please see electrical ratings for maximum voltage and 
table below for current. 
 
• The MCCB and breaker protection and fuse ratings (refer to the preceding table) shall be equal to or 
greater than the short-circuit tolerance of the power supply being used. 
• Suitable for use on a circuit capable of delivering not more than (A) RMS symmetrical amperes 
for.DiJ2.lHp in 240 / 480 V class drives motor overload protection. 
 
 
  Inverter Motor Overload Protection 
 
Set parameter 02-01 (motor rated current) to the appropriate value to enable motor overload protection.   
The internal motor overload protection is UL listed and in accordance with the NEC and CEC. 
 
■  02-01 Motor Rated Current 
 
Setting Range Model Dependent 
Factory Default: Model Dependent 
 
The motor rated current parameter (02-01) protects the motor. The motor protection parameter 08-05 is 
set as factory default. Set 02-01 to the full load amps (FLA) as shown on the nameplate of the motor.