4-38
Up/Down keep Frequency status after a stop command
【0】: After a stop command in Up/Down mode, the preset frequency is retained when
the inverter stops, and the UP/Down function is disabled.
【1】: After a stop command in Up/Down mode, the preset frequency is reset to 0 Hz
when the inverter stops.
【2】: After a stop command in Up/Down mode, the preset frequency is retained when
the inverter stops and the UP/Down function remains enabled.
03-07 =【0】,【2】When run signal is removed (Stop Command), the output frequency is stored in parameter
05-01 (Keypad Frequency).
03-07 =【0】 while the inverter is stopped Up/Down mode is disabled and the keypad can be used to change
the frequency (parameter 05-01).
03-07 =【1】When in Up/down frequency mode the inverter will ramp up from 0 Hz on a Run command and
Ramp down to 0 Hz on a stop command.
Multifunction terminals S1~S5 scan time
Sets the digital input CPU scan time. The digital input needs to be present for the minimum scan time to qualify
as a valid command.
Scan period unit in milliseconds.
Use this parameter in noisy environments, note longer scan time results in slower response time for inputs.
S1~S5 Input type selection NO & NC
【xxxx0】:S1 NO 【xxxx1】:S1 NC
【xxx0x】:S2 NO 【xxx1x】:S2 NC
【xx0xx】:S3 NO 【xx1xx】:S3 NC
【x0xxx】:S4 NO 【x1xxx】:S4 NC
【0xxxx】:S5 NO 【1xxxx】:S5 NC
(NO) Normally open, (NC) normally closed. Select as required by the application.
Select Normally Open (NO) or Normally Closed (NC) by setting the corresponding digit in parameter
03-09 to 0 or 1.
Set Parameter 03-09 first before setting parameters 00-02/00-03=1 (Run mode from terminals).
Multifunction Output Relay RY1 functions. ( Terminals RA, RB )
【0】:Run
【1】:Fault
【2】:Setting Frequency Reached (Refer to 03-14)
【3】:Frequency Reached (3-13±3-14) (Refer to 03-13/03-14)
【4】:Output Frequency Detection 1 (> 03-13) (Refer to 03-13)
【5】:Output Frequency Detection 2 (< 03-13) (Refer to 03-13)
【6】:Auto-Restart
【7】:Momentary AC Power Loss (Refer to 07-00)
【8】:Rapid Stop (Decelerate to Stop)
【9】:Base Block