4-39
【10】:Motor Overload Protection (OL1)
【11】:Drive Overload Protection (OL2)
【12】:Reserved
【13】:Output Current Reached (refer to 03-15/03-16)
【14】:Brake Control (refer to 03-17/03-18)
【15】:PID Feedback Disconnection Detection (refer to 10-11/10-13)
Frequency Detection Level
Frequency Detection Width
Output relay RY1. Function descriptions:
1) 03-11 =【0】RY1 output is active during running.
2) 03-11 =【1】RY1 output is active during fault condition.
3) 03-11 =【2】RY1 output is active when the output frequency falls within the setting frequency minus the
frequency detection width (o3-14).
FWD
REV
Setting Freq.
(03-14)
When Output Freq. = Setting Frequency –
Frequency Detection Width (03-14),
Relay Output will be ON.
Output Freq.
ON ON
Relay Output
Hz
Time
0
RUN RUN
Run Command
Setting Freq. – (03-14)
(03-14)
Setting Freq. + (03-14)
Setting Freq.
Example:
Setting Freq. set to 30 Hz, and Frequency Detection Width (03-14) set to 5 Hz.
Relay is ON when the output frequency >=25 Hz and <= 30Hz and a Run Command is present (Allowable
tolerance ±0.01).