4-43
04-External Analog Input / Output Parameter
04-00
Analog Voltage & Current input selections
Range
AVI ACI
0:0~10V 0~20mA
1:0~10V 4~20mA
2:2~10V 0~20mA
3:2~10V 4~20mA
Analog Input Scaling formulas:
AVI (0~10V), ACI (0~20mA)
V (v)
AVI (0 - 10V): F (Hz) = x (00-12)
10 (v)
I (mA)
ACI (0 - 20mA): F (Hz) = x (00-12)
20 (mA)
AVI (2~10V), ACI (420mA)
V 2 (v)
AVI (2 - 10V): F (Hz) = x (00-12) (V>=2)
10 - 2 (v)
I 4 (mA)
ACI (4 - 20mA): F (Hz) = x (00-12) (I>=4)
20 - 4 (mA)