4-44
AVI signal verification Scan Time
【0】: Positive 【1】: Negative
【0】: Positive 【1】: Negative
ACI signal verification Scan Time
【0】: Positive 【1】: Negative
【0】: Positive 【1】: Negative
Set 04-01 and 04-06 for Analog signal scan and filtering time.
Inverter reads the average values of A/D signal once every 04-01/04-06 x 1ms.
Set scan intervals based on the application environment for signal instability and/or signal interference caused by
external sources. Note: Long scan times will result in slower response times.
AVI: Analog Voltage input scaling examples adjusting Gain, Bias & Slope parameters (04-02~04-05).
(1) Positive Bias type (04-04 = 0) showing the effects of modifying Bias parameter 04-03 and Slope type
parameter 04-05 as shown in Fig 1 & 2.
Figure 1: Figure 2:
60Hz
30Hz
0Hz
0V 5V 10V
Hz
V
04-03
Bias
100%
50%
0%
Upper
Frequency
A
B
60Hz
30Hz
0Hz
0V 5V 10V
Hz
V
100%
50%
0%
C
D
04-03
Bias