4-47
04-11
Analog Output (AO) function selection.
Range
0:Output frequency
1:Frequency Setting
2:Output voltage
3:DC Bus Voltage
4:Output current
Example: Set 04-11 required according to the following table.
0
10V
Xmax
A
Xmax( 04-11)
Xmax/2
5 V
04-12
AO Gain
Range
0 ~ 1000%
04-13
AO Bias
Range
0 ~ 100%
04-14
AO Bias Selection
Range
0: Positive 1: Negative
04-15
AO Slope
Range
0: Positive 1: Negative
Use parameter 04-11 to select the analog output signal for AO. Output range is 0-10Vdc.
The output voltage level can be adjusted using parameters 04-12 to 04-15.
For examples on gain and bias adjustment see Analog Voltage Input (AVI) parameters 4-02 to 4-05.
Note: The maximum output voltage of 10V is limited by the inverter hardware. Use external devices that can handle a
maximum of 10Vdc signal.
04-11
A
10V =xMax
0
Output frequency
Maximum output frequency
1
Frequency Setting
Maximum output frequency
2
Output voltage
Motor Rated Voltage
3
DC Bus Voltage
230V: 0 ~ 400Vdc
460V: 0 ~ 800Vdc
4
Output current
2 x inverter rated current