4-49
SLV mode:
Actual Acc time=
Time of Accel1 or 2 x Preset Frequency
Motor rated output frequency
Actual Dec time=
Time of Accel1 or 2 x Preset Frequency
Motor rated output frequency
V/F Maximum output frequency set by parameter 01-02 when custom V/F is selected by 01-00 =【7】.
V/F Maximum output frequency = 50.00 Hz or 60.00 Hz when preset V/F patterns are selected. 01-00 =【1 to 6】.
Preset speed 1 Actual Accel time=
(05-19) X 10(Hz)
01-02
Example:01- 00≠【7】, 01- 02=【50】Hz, 05- 02=【10】Hz (preset speed1),
05-19=【5】s(Accel time), 05-20=【20】s (Decel time)
= 1(s)
Preset speed 1 Actual Deccel time=
(05-20) X 10(Hz)
01-02
= 4(s)
Multi speed run/stop cycles with Individual accel/decel times. 05-00=【1】
Two modes of operation:
Mode1 = On/Off run command
Mode2 = Continuous run command
Mode1 Example: 00-02=【1】(External Run/Stop Control).
00-04=【1】(Operation Mode:Run/stop-forward/reverse).
S1: 03-00=【0】(RUN/STOP );
S2: 03-01=【1】(Forward/Reverse);
S3: 03-02=【2】(Preset speed 1);
S4: 03-03=【3】(Preset speed 2);
S5: 03-04=【4】(Preset speed 4);
Acceleration / Deceleration Calculation Mode 1:
If the run command is cycled on and off, acceleration and deceleration time (a ~ f) is calculated based on the
active speed command as follows: