4-53
Auto Run sequencer mode can be enabled by setting any of the multifunctional input parameter 03-00 to
03-04for S1 to S5 to selection18.
Various Auto Run (sequencer) modes can be selected with parameter (06-00).
7 Auto Run (sequencer) modes can be selected with parameters (06-01~06-39).
Auto Run frequency commands1 to 7 are set with Parameters (06-01 ~ 06-07).
Sequence run times are set with parameters (06-17 ~ 06-23).
FWD/REV Direction for each sequence can be set with parameters (06-33 ~ 06-39).
Auto sequence 0 uses keypad frequency parameter 05-01; sequence run time and direction are set by
parameters 06-16 and 06-32.
Auto RUN (Auto Sequencer) Examples:
Example 1: Automatic operation mode Single cycle
The inverter will run for a single full cycle based on the specified number of sequences, then it will stop. In this
example 4 sequences are set, three in forward direction and one in Reverse.
Auto Run Mode: 06-00 =1or4,
Frequency : 05-01 =15Hz, 06-01 =30Hz, 06-02 =50Hz, 06-03 =20Hz
Sequence Run Time: 06-16 =20s, 06-17 =25s, 06-18 =30s, 06-19 =40s,
Direction: 06-32 =1FWD, 06-33 =1FWD, 06-34 =1(FWD), 06-35 =2(REV)
Unused Sequence Parameters: 06-04~ 06-07 =0Hz, 06-20~06-23 =0s, 06-36~06-39 =0
05-01
06-01
06-02
06-03
06-16
06-17
06-18
06-19
T
Hz
RUN command
RUN
ON
S1 to S5 auto
run enable