4-55
Example 3: Automatic operation mode – Single cycle and continue running at last speed of the cycle
In this example the inverter executes a single cycle and continue running at last speed of the cycle.
Auto Run Mode: 06-00 =【3】or【6】
Frequency: 05-01 =【15】Hz, 06-01 =【30】Hz, 06-02=【50】Hz, 06-07 =【20】Hz,
Sequence Run Time: 06-16 =【20】s, 06-17 =【25】s, 06-18 =【30】s, 06-23 =【40】s,
Direction: 06-32 =【1】FWD, 06-33 =【1】, 06-34 =【1】, 06-39=【1】,
Unused Sequence Parameters 06-03~06-06 =【0】Hz, 06-19~06-22 =【0】s, 06-35~06-38 =【0】
05-01
06-01
06-02
06-16 06-17 06-18 06-23
Hz
06-07
T
RUN
Command
RUN
RUN
S1 to S5 auto
run enable