4-11
Group 01-
/F Pattern selection & Setup
No. Description Range
Factory
Setting
Unit Note
01-00
Volts/Hz Patterns 1~7 1/4 -
01-01
V/F Max voltage
200V:170.0~264.0
400V:323.0~528.0
Based on 13-08 Vac
01-02
Max Frequency 0.2 ~ 599.00 50.00/60.00 Hz
01-03
Max Frequency Voltage Ratio 0.0 ~ 100.0 100.0 %
01-04
Mid Frequency 2 0.1 ~ 599.00 2.50/3.00 Hz
01-05
Mid Frequency Voltage Ratio 2 0.0 ~ 100.0 10.0/6.8 %
01-06
Mid Frequency 1 0.1 ~ 599.00 2.50/3.00 Hz
01-07
Mid Frequency Voltage Ratio 1 0.0 ~ 100.0 10.0/6.8 %
01-08
Min Frequency 0.1 ~ 599.00 1.30/1.50 Hz
01-09
Min Frequency Voltage Ratio 0.0 ~ 100.0 8.0/3.4 %
01-10
Volts/Hz Curve Modification
(Torque Boost)
0 ~ 10.0 0.0 % *1
01-11
V/F start Frequency 0.00~10.00 0.00 Hz
01-12
No-load oscillation suppression
gain
0.0~200.0 0 %
01-13
Motor Hunting Prevention
Coefficient
1~8192 800
01-14
Motor Hunting Prevention Gain 0~100
Frame1/2 100V/200V
series: 7
others: 0
%
01-15
Motor Hunting Prevention Limit 0~100.0 5.0 %
01-16
Auto-Torque Compensation
Filter Coefficient 0.1~1000.0
0.1 ms
01-17
Auto-torque Compensation
Gain
0~100 0 %
01-18
Auto-torque Compensation
Frequency
1.30~5.00 2 Hz