4-24
Group11- Performance Control functions
No. Description Range
Factory
Setting
unit Note
11-00
Reverse operation control
0: Reverse command is valid
1: Reverse command is invalid
0 -
11-01
Carrier Frequency (kHz) 1~16 5 KHz
11-02
Carrier mode Selection
0: Mode0, 3phase PWM modulation
1: Mode1, 2phase PWM modulation
2: Mode2, random PWM modulation
1 -
11-03
Carrier Frequency
Reduction by temperature rise
0: Disabled
1: Enabled
0 -
11-04
S-Curve Acc 1 0.0 ~ 4.0 0.00 s
11-05
S-Curve Acc 2 0.0 ~ 4.0 0.00 s
11-06
S-Curve Dec 3 0.0 ~ 4.0 0.00 s
11-07
S-Curve Dec 4 0.0 ~ 4.0 0.00 s
11-08
Skip Frequency 1 0.00 ~ 599.00 0.00 Hz *1
11-09
Skip Frequency 2
0.00 ~ 599.00
0.00 Hz *1
11-10
Skip Frequency 3
0.00 ~ 599.00
0.00 Hz *1
11-11
Skip Frequency Bandwidth (±) 0.00 ~ 30.00 0.00 Hz *1
11-12
Reserved
11-13
Regeneration Prevention
Function
0: Disable
1: Enable
2: Enable (during constant speed only)
0 -
11-14
Regeneration Prevention
Voltage Level
200v: 300.0~400.0
400v: 600.0~800.0
380/760 V
11-15
Regeneration Prevention
Frequency Limit
0.00~15.00 3.00 Hz
11-16
Regeneration Prevention
Voltage Gain
0~200 100 %
11-17
Regeneration Prevention
Frequency Gain
0~200 100 %
11-18
Speed loop proportion gain
0~65535 10000
11-19
Speed loop integration gain
0 ~65535 800
11-20
Speed loop differential gain
0 ~65535 0
11-21
Stop Key Selection
0: Enable Stop Key when Run Command
not from Keypad
1: Disable Stop Key when Run Command
not from Keypad
0