00-12 Frequency Upper limit
Range
【0.01~599.00】Hz
00-13 Frequency Lower limit
Range
【0.00~598.99】Hz
When 00-13 and the command frequency are both set to 0.00, if RUN is pressed ” Stpo” is
displayed.
When Frequency command is > than preset in 00-13 inverter output will ramp up from 0.00 to the
command frequency.
When 00-13> 0, and the frequency command value ≤ 00-13, inverter output will ramp up from
preset in lower limit to the command frequency.
Frequency upper limit
Frequency Lower limit
0
Hz
T
00-14
Acceleration time 1
Range
【0.1~3600.0】s
00-15 Deceleration time 1
Range
【0.1~3600.0】s
00-16 Acceleration time 2
Range
【0.1~3600.0】s
00-17 Deceleration time 2
Range
【0.1~3600.0】s
Preset Acceleration and Deceleration times by above parameters are the time taken for the output
frequency to ramp up or ramp down between the Upper and the lower V/F frequency limits.
Actual acceleration and deceleration time is calculated as follows:
V/F mode:
SLV mode: