4-22
and then ON again, or press the run key in keypad mode, the inverter will restart again up and ramps
up to the command frequency.
If the emergency signal is released before the inverter stops completely, the inverter still carries out
the emergency stop.
E.01-00~ 04=7: Base Block
The inverter immediately stops output, and the motor does a Coast with flashing B.B.
F.01-00~04=8(Reset Command)
The Reset command is same as the Reset Key on the panel. When the command is OFF, the inverter
does not respond.
G.01-00~04=9
Automatic program operation is generally simple built-in PLC function, when the external terminal
set to 9, the general principles of the terminal guided 13 groups of related setting and complete
function of automatic program running, refer to 13 groups.
H. 01-00~04=10/11(Speed up / Slow Down)
Increase or decrease the reference value by set in the parameter 01-05 acceleration/deceleration
value by percentage (relative)
01- 06 Speed up / Slow Down Value
range
【1~100】%
Enter a relative percentage value to be added to the actual rise or deceleration reference value or
subtract from it.
The actual frequency input value = Frequency input value + Frequency input value×(parameter
01-05)
01- 06 Digital /Analog input signal scan times
range
【1~200】2mSec
1).TM2 terminal is used for scanning. If there are the same signals continuously input for N times, the
inverter will treat the signal as normal. During the signal evaluation, if the scan times are less than N,
the signal will be treated as noise.
2).Each scan period is 2ms.
3). The user can specify the scan times interval duration according to the noise environment. If the
noise is serious, increase the value of 01-06, however the response will be slower.
01- 07 Step of Up/Down Function
range
【0.00~5.00】Hz
There are two modes covered below:
1).01-07 = 0.00, the operation is just as the original one. When the UP terminal is ON, the frequency increases while
the DOWN terminal is ON, the frequency decreases. (Refer to the following graph).
2). 01-07 = 0.01 to 5.00, and UP/ DOWN terminal ON, is equivalent to a step increase/ decrease at the increment
frequency in 01-07. If UP/DOWN is pressed over 2 seconds, the original UP/DOWN mode is restored (Please refer
to the following diagram)