4-45
3) When pressing ‘Reset’ at 12-02, the three fault log will be cleared when the reset key is
pressed. The log content will change to 1. ---, 2. ---, 3. ---.
4) E.g. the fault log content is ‘1.OC-C’; this indicates the latest fault is OC-C, etc.
12- 03 Accumulated Operation Time 1 (Hours)
Range
【0~23】Hours
12- 04 Accumulated Operation Time 2 (Days)
Range
【0~65535】Days
12- 05 Accumulated Operation Time Mode
Range
【0】:Power on time
【1】:Operation tim
1) When the operation time is to 23 as the elapsed time 1 is set. The next hour will be carried to
operation12-04. Meanwhile, the recorded value will be cleared to 0000, and the record value of
operation duration 2 will be 01.
2) Description of operation time selection:
Preset value
Description
0
Power on, count the accumulated time.
1
Inverter operation, count the accumulated operation time.
12- 06 Reset Drive to Default Settings
Range
【1150】:Reset to the 50Hz factory setting
【1160】:Reset to the 60Hz factory setting
12- 07 Parameter lock
Range
【0】:Enable all Functions
【1】: 03-01~03-16 cannot be changed
【2】:All Functions cannot be changed Except 03-01~ 03-16
【3】:Disable All Function
Group13- Auto Run (Auto Sequencer) function group
13- 00
Auto Run( sequencer) mode selection:
Range
【0】:Disabled.
【1】:Single cycle.(Continues to run from the unfinished step if restarted).
【2】:Periodic cycle.(Continues to run from the unfinished step if restarted).
【3】:Single cycle, then holds the speed Of final step to run. (Continues to run from the
unfinished step if restarted).
【4】:Single cycle. (Starts a new cycle if restarted).
【5】:Periodic cycle. (Starts a new cycle if restarted).
【6】:Single cycle, then hold the speed of final step to run. (Starts a new cycle if restarted).
Frequency Command 0 is set by parameter 05-01.
13- 01~13-07
Frequency Command 1~7 speed setting.
Range
【0.00 ~ 650.00】Hz
13- 16~13-23
Set the running time of Frequency Command 0 and 7
Range
【0.00 ~ 3600.0】Sec
13- 32~13-39
Set the direction of Frequency Command 0 and 7
Range
【0】:stop 【1】:foreward 【2】:backward