50
Protection function Explanation
LCD display
(English)
External baseblock signal
input (Minor failure)
main circuit transistor
instantance shut-off
When an external base block signal is input, the motor coasts to a stop. When the
external base block signal is removed, the inverter output is immediately turned
on at the previously set frequency.
(blinking)
Alarm (bb)*
1
B.B.
lnvaid parameter setting
When an invalid parameter is set, it is indicated on the monitor at power up or
when the inverter is changed from the PRGM mode to the DRIVE mode.
Alarm (OPE01)*
1
Set Cap. Error
Alarm (OPE02)*
1
Parameter Incorrect
Alarm (OPE03)*
1
I/P Term. Incorrect
Alarm (OPE10)*
1
V/F curve Incorrect
Alarm (OPE11)*
1
Carry-Freq Incorrect
Parameter read error Parameter read error
Alarm (Err)*
1
Read Error
RS-485
Communication
Fault
Fault 1
RS-485 Communication error or transmission fault during communicating and the
Rs-485 stopping method after communication error of Sn-08 is to continue to run
(Sn-08=11xx)
(blinking) (CPF21)*
1
Comm Fault 1
Fault 2
RS-485 Communication protocol error and the RS-485 stopping method after
communication error of Sn-08 is to continue to run (Sn-08=11xx)
(blinking) (CPF22)*
1
Comm Fault 2
RS-485 Communication
Ready
When the inverter with communication option card (PA-M, PA-P, PA-C or PA-L)
does not receive correct data from master controller.
(CALL)*
1
Comm Stand by