51
Fault Contact
output
Error causes Action to be taken
Non Operation
- -
Non Operation
Inverter KVA setting (Sn-01) error
Review the parameter setting range and conditions
Parameter setting range error
Multi-function contact input setting error
(Sn-15 ~ Sn-18)
Improper setting of V/F characteristic
(Cn-02 ~ Cn-08)
Improper setting of carrier frequency
(Cn-23 ~ Cn-25)
Non Operation
EEPROM internal data did not match when initializing the
constant
Turn off power, then turn on again. If error is
persistent, replace the control board.
Non Operation
RS-485 communication option card fault.
Excess vibration or shock.
External noise
Turn off power, then turn on again. If error is
persistent, replace the option card.
Non Operation
The RS-485 communication protocols setting in inverter (Sn-
24) and option card are in consistent.
Check the setting in Sn-24 and option card.
Non Operation
Poor connection
Defective communication software (in master controller)
Check for communication cable between
communication option card and master controller
(PLC)
Check for communication software.