EasyManua.ls Logo

Teledyne 300E - Control Inputs; Table 6-12: Status Output Pin Assignments

Teledyne 300E
253 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model 300E Carbon Monoxide Analyzer
Instruction Manual
Operating Instructions
P/N 04288 REV: A 87
The pin assignments for the Status Outputs are:
Table 6–12: Status Output Pin Assignments
Output #
Status
Definition
Condition
1 SYSTEM OK On if no faults are present.
2
CONC VALID
On if CO concentration measurement is valid.
If the CO concentration measurement is invalid, this bit is OFF.
3 HIGH RANGE On if unit is in high range of DUAL or AUTO Range Modes.
4 ZERO CAL On whenever the instruments ZERO point is being calibrated.
5 SPAN CAL On whenever the instruments SPAN point is being calibrated.
6 DIAG MODE On whenever the instrument is in DIAGNOSTIC mode.
7 SPARE
8 SPARE
D
EMITER BUSS The emitters of the transistors on pins 1-8 are bussed together.
+ DC POWER + 5 VDC
Digital Ground
The ground level from the analyzer’s internal DC Power
Supplies.
6.7.2. Control Inputs
Several Control Inputs are provided via an 10-pin connector labeled CONTROL IN
on the analyzer’s rear panel. These are opto-isolated digital inputs that are
activated when a 5 VDC signal is applied to the “+” pin.
These inputs allow the user to remotely initiate Zero and Span calibrations. Two
methods for energizing the inputs is provided below; the first using the internal
+5V available on the CONTROL IN connector and the second, if an external,
isolated supply is employed.

Table of Contents