ADR-7000 / SAVER-7000 / GUARD-7
© 2017 – Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017
– Page 32 of 87 –
Note
Re-fill or replace the extinguishing device, enter programming mode and
return the control panel to normal operation select 5 Utilities on the main
menu and then 2 Clear Activated Extinguisher in order to return the control
panel to normal operation.
This action shall be performed by authorized personnel.
Ensure that the control panel is back to normal operation.
UL Requirement
UL 864 paragraph 36.1.7 states that "An automatic delay provided prior to
release operation by a system shall be a maximum of 60 seconds, timed from
a release initiation condition, either from the actuation of a single detector, or
from the actuation of the second circuit or detector for cross-zone and single-
zone multiple-detector, or a combination of the two operations"
Warning
Connect only extinguishing devices that are authorized by Telefire and
the authority having jurisdiction.