9.5 Programming Faults
Error Messages
Possible Cause
Repair Action
<address> exists, not
programmed
There is a device attached to
the addressable circuit that
was not programmed
Program the device in, open
system programming,
programming devices, and
add the device.
<address> same
address
There are two devices with
the same address
Run diagnostics. The control
panel will turn on a red
indicator light on all the
devices with the same
address. Change
the address for one of the
devices using PROG 4000.
Device Matrix: the
number of devices is
lower than the number
of alarms
Alarm conditions cannot be
met because the requirement
is that there have to be more
alarms than the number of
devices defined within the
matrix
Reduce the number of input
devices required activate the
output or add input devices to
the operation matrix
Input device listed in
matrix has been
cancelled
This message will be
received when the one of the
system's input devices is
removed, but the device still
belongs to the activation
matrix of the output device
Disabled
A device or area is disabled
If you want to turn on the
device:
Open start/stop device menu
from the main menu, select
the device or the
area indicated in
the message, and click
Enable.
Supervisory output
circuit without a
supervisory switch in a
selected area
An output circuit has been
defined as a Supervisory
output circuit, but a
supervisory switch has not
been defined in the same
area
Define a supervisory switch in
the same area as a
supervisory output circuit
define the switch as an
ordinary switch (siren,
light, etc.)
The extinguishing output
circuit cannot be
programmed as a
general output circuit
A mistake in the
extinguishing output circuit
definitions
Define the operating
conditions as a matrix