8.4.5 Device Listing
Screen 28 System reports device report
Device List report allows you to check device quantities. You can check all loops, a
specific loop, and either all devices or a specific device type, such as heat detector r
sounder. Selection is the same process used in enable / disable device.
8.4.6 Active Output
Active Outputs report indicates outputs that are active at the moment. You can select all
loops, a specific loop, and either all devices or a specific device type (sounder; Lamp;
Extinguisher; Extinguisher Control; Control Out; Supervisory Out; or Fire Phone Lamp).
Screen 29 System reports active outputs
8.4.7 Maintenance Recommendations
Maintenance recommendation report lists all detectors that are close to maintenance
alarm. You can select all loops; a specific loop; a specific logical zone; and smoke
detectors, photo / heat detectors, or both.
Screen 30 System reports Maintenance recommendation
i
Note
It is recommended to replace detectors that are close to maintenance alarm
(detectors whose reference value Vref is equal or lower than 65).