ADR-7000 / SAVER-7000 / GUARD-7
© 2017 Telefire Fire & Gas Detectors Ltd Revision 0.98 October 2017
Page 58 of 87
8.9.12 Remote Displays
This menu configures the RM-7000 remote anunciators. You can select whether each of
the 16 RM-7000 is active or not; Class A or Class B wiring; and assign a 19 character
description to each RM-7000.
Screen 57 System configuration remote displays
8.9.13 COM Ports
This menu allows you to select the operation mode of COM1, COM2, and COM5 as
inactive, active an PC communication or NET-7000 TCP/IP interface; whether the
communication is supervised or not; and Baud rate.
COM3 and COM4 are used as RM-7000 connections and can't be configured other than
Class B or Class A operation (see above).
Screen 58 System configuration com ports
8.9.14 LON Card
This menu allows the configuration of the LON-7000 port.
Screen 59 System configuration LON cards
8.9.15 Loop Expansion Card
This menu allows you to configure whether an ADR-7022 SLC Expansion Module (for
loops 5 8) is installed.