Teze TW-EOR48 - Battery Charging and Type Settings; Battery Charging Current and Type; Battery Voltage Settings; Battery Equalization Settings

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Add: Building A, Xinlida Industrial Park, Junzibu Village,Guanlan Street, Longhua District ,Shenzhen,
Guangdong
TEL :0755-23225527 FAX:0755-23225537
26
is sufficient, the utility stops charging.
Note: The PV and mains can only be charged at the
same time when the mains bypass output is loaded.
When the inverter is operating, only PV charging can
be initiated, not utility charging.
CUB
Utility is the first priority in charging, PV charging the
battery only when utility is not available.
CSO
PV is the first priority in charging, utility charging the
battery only when solar power is not sufficient.
OSO
PV charging only, no utility charging.
07
Battery charging
current
120A default
Setting range 0~220A
08
Battery type
USER
User-defined, user can set all battery parameter
SLd
Sealed lead-acid battery.
FLd
Flooded lead-acid battery.
GEL default
Gel lead-acid battery.
L14/ L15/ L16
LFP li-ion battery, 14\15\16 corresponds battery cells
number in series.
N13/ N14
Ternary li-ion battery.
09
Battery bulk charging
voltage
57.6 default
Setting range 48V~58.4V, step 0.4V, valid when battery
type is custom and lithium battery.
11
Battery float charging
voltage
55.2 default
Setting range 48V~58.4V, step 0.4V, this parameter can
not be set after the BMS communication is successful.
12
Battery over- discharge
voltage (delay off)
42 default
When the battery voltage is lower than the judgement
point, and triggers the parameter [13], the inverter
output is switched off, the setting range is 40V~48V,
the step is 0.4V, valid when battery type is custom and
lithium battery.
13
Battery over- discharge
voltage delay time
5 default
The battery voltage is lower than parameter [12], and
the inverter output is switched off after triggering the
delay time set in this parameter, the setting range is
5S~50S, the step is 5S, valid when battery type is
custom and lithium battery.
14
Battery under- voltage
alarm
44 default
When the battery voltage is lower than this judgement
point, the device will under-voltage alarm, the output
will not be switched off, the setting range is 40V~52V,
the step is 0.4V, valid when battery type is custom and
lithium battery.
15
Battery under-voltage
limit voltage
40 default
When the battery voltage is lower than the value of
this parameter item, the output will be switched off
immediately. Setting range 40V~52V, step 0.4V, valid
when battery type is custom and lithium battery.
16
Battery equalization
charging
DIS
Disable equalization charging.
ENA default
Enable equalization charging, parameter can be set
only when battery type is FLd\SLd\USER.
17
Battery equalization
charging voltage
58
Setting range: 48V~58V, increment of each click is
0.4V, parameter can be set only when battery type is
FLd\SLd\USER.
18
Battery equalization
charging duration
120
Setting range: 5min~900min, increment of each click is
5min, parameter can be set only when battery type is
FLd\SLd\USER.
19
Battery equalization
120
Setting range: 5min~900min, increment of each click is