27
charging delay time
5min, parameter can be set only when battery type is
FLd\SLd\USER.
20
Battery equalization
charging interval
30
Setting range: 0~30days, increment of each click is
1day, parameter can be set only when battery type is
FLd\SLd\USER.
21
Battery equalization
charging stop-start
DIS default
Start equalization charging immediately.
ENA
Stop equalization charging immediately.
22
Power saving mode
DIS default
Disable power saving mode.
ENA
Enable energy-saving mode, when the load power is
less than 25W, the output of the inverter will switch off
after a 5-minute delay. When the load exceeds 25W,
the inverter will restart automatically.
23
Over-load restart
DIS
Disable overload automatic restart, if an overload
occurs to shut down the output, the machine will not
be restored to power on again.
ENA default
Enable overload automatic restart. If an overload
occurs that shuts down the output, the machine delays
for 3 minutes before restarting the output. After
accumulating 5 times, it will not restart again.
24
Over-temperature
restart
DIS
Disable over-temperature automatic restart, if over-
temperature occurs to switch off the output machine
no longer switch on the output.
ENA default
Enable over-temperature automatic restart, if over-
temperature occurs the output is switched off, it will
be switched on when the temperature drops.
25
Buzzer alarm
DIS
Disable buzzer alarm.
ENA default
Enable buzzer alarm.
26
Power source switching
reminder
DIS
Disable reminder when the status of the input power
source changes.
ENA default
Enable alert when the status of the main input source
changes.
27
Inverter overload
switch to bypass
DIS
Disable automatic switching to mains to power the
load in the event of an inverter overload.
ENA default
Automatic switching to mains to power the load in the
event of an inverter overload.
28
Max. utility charging
current
120A
Setting range: 0~120A.
30
RS485 address
ID:1
RS485 address setting range: 1~254.
32
RS485 communication
SLA default
RS485 PC & Remote Monitoring Protocol.
BMS
RS485 BMS communication function.
CAN
CAN BMS communication function.
33
BMS communication
When item [32] = BMS, the corresponding lithium battery manufacturer
brand should be selected for communication.
WOW default
PAC=PACE, RDA=RITAR, AOG=ALLGRAND
OLT=OLITER, CEF=CFE, XYD=SUNWODA, DAQ=DYNESS,
WOW=SRNE, PYL=PYLONTECH POW=POWMr,
UOL=VILION.
34
Feed back & hybrid
output function
DIS default
Disable this function.
MIX LOD
When parameter [01]=UTI, the solar energy is
prioritised to charge the battery and any excess energy
will be used to power the load. With an anti-backflow
function, the PV energy is not feed back into the grid.