EasyManuals Logo

THOMSON TSC 800 - V2.2 User Manual

THOMSON TSC 800 - V2.2
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background imageLoading...
Page #50 background image
TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 10 08/09/25 Thomson Technology
44
7.3.3. UTILITY FAIL CALLOUT
NOTE:
The following features are viewable only in Master Read / Write Mode in
TSC 800 Software version 2.0 (or higher).
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when a Utility (Source 1) power failure is
detected. The callout signal will be reset when the Utility (Source 1)
power returns to normal condition.
DISABLED: The controller will not initiate a callout when a Utility (Source 1) power
failure is detected.
7.3.4. LOAD ON GENERATOR CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when the load is connected to the generator
supply. The callout signal will be reset when the load transfers back to
the utility supply.
DISABLED: The controller will not initiate a callout when the load transfers to the
generator supply.
7.3.5. TRANSFER FAIL CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.
ENABLED: The controller will initiate a callout signal via the communication port to a
remote connected device when the transfer switch fails to operate. The
callout signal will only reset when the “Fail to Transfer” alarm is manually
reset via local pushbuttons or with the remote communication software.
DISABLED: The controller will not initiate a callout when a “Fail to Transfer alarm
condition occurs.
7.3.6. AUTO TEST CALLOUT
When the remote communication option is enabled, this programming prompt will
appear. This feature may be enabled or disabled by programming selection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.2 and is the answer not in the manual?

THOMSON TSC 800 - V2.2 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.2
CategoryController
LanguageEnglish

Related product manuals