TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 10 08/09/25 Thomson Technology
40
7.1.3. MASTER READ / WRITE MODE
User can view/modify any programming parameter as well as view/modify the security
password level numbers. Consult THOMSON TECHNOLOGY factory for master
password number if required.
To enter the programming mode, follow the procedure as shown:
Program Menu
Yes
Select the Program Menu by scrolling through the display screens using the ENTER or
EXIT pushbuttons. When displayed, use the INCREMENT pushbutton to select the
YES prompt and push the ENTER button.
Password
0
Use the INCREMENT or DECREMENT pushbuttons to ramp the displayed number up
or down to the desired password access number. Press the ENTER pushbutton when
the correct number is displayed.
NOTE:
If an invalid number is entered, programming access will be
limited to time clock adjustment only. To exit the programming
mode, press the EXIT pushbutton and hold for two seconds
until the display scrolls rapidly.
When the programming mode is accessed, the programming parameters will be
displayed in the same order as the Programming Data Sheet provided with the
transfer switch. To skip over parameters that do not require changes, push and hold
the ENTER pushbutton until the desired function is displayed. The EXIT pushbutton
may be used to scroll backwards through the programming parameter loop, but only
one keystroke at a time, maintaining it longer than 2 seconds will exit the program
menu.
To change a programmed parameter, use the INCREMENT or DECREMENT
pushbuttons to scroll through the available options or to adjust a value up or down to
the desired number. When the desired option or number is displayed, press the
ENTER pushbutton to accept the new value. Pressing the EXIT pushbutton after a