TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 10 08/09/25 Thomson Technology
76
10. TSC 800 SPECIFICATIONS
• POWER SUPPLY:
- 115 or 230VAC nominal (+10% -30%)
- 50/60Hz
- 100ma nominal (no external load connected)
• SOURCE VOLTAGE SENSING:
- Direct 120-600VAC nominal, single or three phase
- 50/60Hz
- +/- 0.5% accuracy of setting @ 25°C
• OPERATING TEMPERATURE:
- 15°C to +50°C
• OUTPUT CONTACTS (Form C, 10A,120/250VAC resistive)
- Engine start
- Programmable function (not available with dual source
system logic or insulated case transfer switches)
• OUTPUT SIGNALS (120/250VAC resistive load)
- Transfer to utility 10A
- Transfer to generator 10A
- Pre/post-transfer to utility 3A
- Pre/post-transfer to generator 3A
- Load on utility 3A
- Load on generator 3A