EasyManua.ls Logo

Toshiba HX7+ ASD - Page 168

Toshiba HX7+ ASD
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HX7+ ASD Installation and Operation Manual 159
Pattern Run
Program Pattern Run Pattern Run
This parameter Enables/Disables the Pattern Run mode. When enabled, this
feature allows up to 15 Preset Speeds to be run sequentially for a user-
determined duration and number of times.
Settings:
0 — Disabled
1 — Enabled (box checked)
Pattern Run Description
User-defined Preset Speeds are labeled 1 – 15 (see F018). The ID number of
any one of the fifteen frequencies (1 – 15) may be entered into the Speed # field
of the Pattern Run screen and run for the number of times entered into the
Repeat field (see
F530). The execution of grouped Preset Speeds in this
manner is called a Pattern Run.
Skip may be selected to ignore a Speed # field.
Pattern Run Setup
1. Configure an unused discrete input terminal for Pattern #1 (2, 3, or 4). This
terminal will initiate the selected Pattern Run. The input terminal settings
may be configured via Program Terminal Selection Input Terminals
(see
Table 14 on pg. 189 for available input terminal settings).
2. Enable the Pattern Run mode of operation via Program Pattern Run 
Pattern Run Pattern Run Mode (Enable/Disable check box).
3. Configure the Preset Speeds that are to be used as the Group Speed set of
frequencies via Program Pattern Run Preset Speeds (e.g.,
Preset
Speed #1 on pg. 79).
4. Configure the Group Speeds by associating the Preset Speeds that are to
be enabled and grouped (from step 3) as Group Speed 1 (2, 3, or 4) via
Program Pattern Run Speeds. Set the Repeat field to the number of
times that the selected group is to be run. Set unused speed settings to Skip.
5. From the Remote mode (Local|Remote light is off), initiate a Run
command (e.g., F and/or R terminal On).
6. Connect the input terminal that was configured in step 1 to CC and the
Pattern Run will start and continue as programmed. Open the connection
to stop the Pattern Run before its conclusion.
See F018 for further information on this parameter.
Direct Access Number — F520
Parameter Type — Check Box
Factory Default Disabled
Changeable During Run — No
Pattern Run Mode Restart Command
Program Pattern Run Pattern Run
This parameter sets the start condition of subsequent Pattern Runs after the
initial Pattern Run has been terminated or has completed its programming.
Settings:
0 — Reset
1 — Continue
Direct Access Number — F521
Parameter Type — Selection List
Factory Default Disabled
Changeable During Run — No
F520 F521

Table of Contents

Other manuals for Toshiba HX7+ ASD

Related product manuals