Page 16 GENERAL DESCRIPTION
E.
Outgoing Load Connections
Connections for outgoing load cable are
located at the rear of each controller
compartment just above the current
transformers. Cables may enter the controller
from either the top or bottom of the enclosure
through the
provided.
If no specific information is provided when the
equipment is ordered regarding the type of load
cables to be used and the direction of entry,
the standard termination assembly shown in
Fig. 15 and Fig. 16 is supplied. Non-shielded
cables sized up one 350MCM per phase can be
accommodated entering either from the top or
bottom of the enclosure (Fig. 15).
This
arrangement can also accept shielded cables
entering from the top sized up to one
350MCM per phase (Fig. 16).
Space is
provided for installation of termination kits
(stress cones) and user-supplied one- or
hole compression type connectors.
When the installation requires termination of
shielded load cables entering from the bottom
of the enclosure, this should be specified when
the equipment is ordered and the termination
assembly shown in Fig. 17 is then provided.
This arrangement can accept shielded or non-
shielded cables up to one 350MCM per phase
entering from the bottom. A field conversion
kit is available to convert from the standard
termination assembly (Fig. 15 and Fig. 16) to
the arrangement shown in Fig. 17. Consult
your local sales representative for information
regarding this kit.
When routing and terminating load cables,
observe the following:
If a ground current sensor (optional)
is supplied with the equipment, route
all of the load cables through the
sensor. Ground wires from shielded
cable terminators must be routed back
through ground sensor window before
attaching to ground bus.
EXIT CABLES
MAX SIZE 350MCM NON-SHI
1
CABLE PER PHASE
BOTTOM EXIT CABLES
MAX
350MCM NON-SHIELDED
1 CABLE PER PHASE
Fig. 15
Non-Shielded Cable Termination
TOP EXIT CABLES
MAX SHIELDED
1 CABLE PER PHASE
SWITCH
Fig. 16 Shielded Cable Termination Top
Entry