GENERAL DESCRIPTION Page 25
CONTROLLER RATINGS
TABLE 2. SHORT-CIRCUIT & WITHSTAND CAPABILITY
Interrupting
Capacity
Amperes)
50,000 RMS
Interrupting
Capacity
MVA)
Short Time
Capability
30
Seconds
2400 A
TABLE 3. CONTINUOUS CURRENT
Short Time
Capability
1 Second
6000 A
Dielectric
Withstand
1 Minute
AC 19
DC 26
Impulse
Voltage
Withstand
BIL
60
Enclosure Type Max. Continuous Amperes Max. Continuous Amperes
One-High Controller or Upper Controller in a
Lower Controller in a High Stacking
High Stacking Arrangement
Arrangement
NEMA-1 Ventilated
I
360
I
320
NEMA-1 Non-Ventilated
I
360
I
280
NEMA-12, 3R 310
280