INSTALLATION
Page 31
CONNECTIONS
Cable and wire bundles that enter the
controller enclosure should be routed to avoid
interference with moving parts. Minimum
bending radius for the type of cable used
should be observed.
Power cables should be braced and/or laced to
withstand short circuit forces wherever such
cables are unsupported. Power cables should
be adequately sized to carry the motor full load
current in accordance with NEC requirements,
and have an adequate voltage rating. Cables
should be dressed and terminated as
appropriate to the voltage class and cable
manufacturer’s recommendations.
Main power bus and horizontal ground bus are
supplied with links to join shipping sections
together. These should be installed in
accordance with Fig. 34 through Fig. 36.
All access covers, barriers, partitions, etc. that
are temporarily removed during installation
must be replaced.
NOTE: Covers and braces supplied only for
protection during shipment should not be
replaced. All debris and tools should be
removed from each compartment as cabling is
completed.
I, I E L I T
Fig. 34 Ground Bus Splice Connections