Page 38 OPERATION
CONTACTOR INSTALLATION
To install the contactor carriage in the
controller:
Lift and pull the release lever out all the
way, then pull out the service drawer
(Fig. 46).
To avoid tipping over,
the controller enclosure
must be securely bolted
to the floor.
Lift and place the contactor carriage on
the service drawer (Fig. 47). The front
of the carriage should line up with the
front of the drawer, and the four
locator pins on top of the drawer
should engage the holes in the bottom
of the carriage. Installation of
contactor carriages in the upper
compartments of two- and three-high
stacking arrangements require the use
of a Toshiba JK lifting device.
Manually lifting heavy
equipment
can
cause
serious injury. Use a
Toshiba JK lifting device.
With the carriage properly in place on
the service drawer, push the drawer
firmly
all the
into the
compartment. Then push the release
lever in until it drops slightly and
latches. This operation causes the load
receptacle to apply bolted pressure to
the load stabs of the carriage.
Fig. 46 Release Lever Disengaged
Fig. 47 Placing The Contactor On The Service Drawer
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com